Betekenis van:
dew point

dew point
Zelfstandig naamwoord
    • the temperature at which the water vapor in the air becomes saturated and condensation begins

    Hyperoniemen

    Werkwoord


    Voorbeeldzinnen

    1. Absolute dew point temperature
    2. Have a wall temperature sufficiently above the dew point of the exhaust gas to prevent condensation.
    3. The sample gas temperature or dew point must not exceed 280 K (7 °C).
    4. The dew point and O2 level of the sampled exhaust stream must be known.
    5. The sample gas temperature or dew point must not exceed 280 K (7 °C).
    6. If water is removed by condensation, the sample gas temperature or dew point shall be monitored either within the water trap or downstream.
    7. The humidity must be maintained to a dew point of 282,5 K ± 3 K (9,5 °C ± 3 °C) and a relative humidity of 45 % ± 8 %.
    8. For sensitive balances, it is recommended that the tolerance for the weighing chamber room air temperature and the dew point be ± 1 K.
    9. Ha may be derived from relative humidity measurement, dew point measurement, vapour pressure measurement or dry/wet bulb measurement using the generally accepted formulae.
    10. The humidity shall be maintained to a dew point of 282,5 (9,5 °C) ± 3 K and a relative humidity of 45 ± 8 %.
    11. The intake air humidity Ha may be derived from relative humidity measurement, dew point measurement, vapour pressure measurement or dry/wet bulb measurement using generally accepted equation.
    12. If water is removed by condensation, the sample gas temperature or dew point must be monitored either within the water trap or downstream.
    13. The humidity shall be maintained to a dew point of 282,5 K ± 3 K (9,5 oC ± 3 oC) and a relative humidity of 45 per cent ± 8 per cent.
    14. The wall temperature of the measuring chamber shall be set to within ± 5 K between 343 K (70 °C) and 373 K (100 °C), but in any case sufficiently above the dew point of the exhaust gas to prevent condensation.
    15. The wall temperature of the measuring chamber must be set to within ± 5 K between 343 K (70 °C) and 373 K (100 °C), but in any case sufficiently above the dew point of the exhaust gas to prevent condensation.